Operational Specifications
-
+/-2°F DRV water temperature control at peak, moderate or zero fixture demand on hot water system designed for continuous recirculation
-
1˚F minimum recirculating water temperature differential
-
LCD display which indicates: set point, delivered temperature, error codes and alarm conditions capable of BAS and mobile connectivity
-
Programmable set point range of 81-158°F (27-70°C) capable of BAS or mobile monitoring and adjustment
-
Programmable thermal disinfection range of 158-185°F (70-85°C)
-
Programmable 1st level hi/lo temp alarm display capable of BAS or mobile alerting
-
Automatic safe closure of hot water inlet in response to: inlet supply failure, 110V power failure, or programmable high temperature error
-
Automatic safe closure of hot water inlet powered by a replaceable lithium battery monitored for low-level alerting