Operational Specifications
-
Ready to go out of the box or field adjustable via Bluetooth® connectivity with the SAGE® mobile app
-
+/-2°F DRV water temperature control at peak, moderate or zero fixture demand on hot water system designed for continuous recirculation
-
1˚F minimum recirculating water temperature differential
-
Programmable set point range of 81-158°F (27-70°C) capable of BAS or SAGE® mobile app for monitoring and adjustment
-
Programmable thermal disinfection range of 158-185°F (70-85°C)
-
Automatic safe closure of hot water inlet in response to: inlet supply failure, 110V power failure, or programmable high temperature error
-
Automatic safe closure of hot water inlet powered by a replaceable lithium battery monitored for low-level alerting