Steam Trap Selection Guides
Applications: Steam Mains & Supply Lines, Tracer Systems, Process Heaters, Modulating Press – Stall, Condensate From Multiple Sources—Open System.
Application |
1st Choice - Best Life-Cycle Performance / Cost |
||||
Valve/Strainer |
SAP/PN |
Steam Trap |
SAP/PN |
||
Connector |
|||||
Steam Mains & Supply Lines |
|
||||
Superheated Temperature |
|
||||
0 ≤ 400 psig (≤ 800°F) |
0 ≤ 27.5 barg (≤427°C) |
IS2 / IS2-BD |
|
SH-2000 |
|
400 ≤ 650 psig (≤ 650°F) |
27.5 ≤ 45 barg (≤ 343°C) |
|
SH-2500 |
|
|
650 ≤ 900 psig (≤ 900°F) |
45 ≤ 62 barg (≤ 382°C) |
IS-4 |
|
SH-4009H |
|
900 ≤ 1,245 psig (≤ 900°F) |
62 ≤ 86 barg (≤ 382°C) |
|
SH-4015 |
|
|
1,245 ≤ 1,800 psig (≤1,050°F) |
86 ≤ 124 barg (≤566°C) |
|
|
SH-1600 |
|
1,800 ≤ 2,700 psig (≤ 900°F) |
124 ≤ 186 barg (≤ 382°C) |
|
|
6155G CV |
|
Steam Mains & Supply Lines |
|
||||
Saturated Temperature |
|||||
0 ≤ 250 psig |
0 ≤ 17 barg |
IS2 |
|
2011-#38 |
|
250 ≤ 400 psig |
17 ≤ 27.5 barg |
|
2011-5/64 |
|
|
400 ≤ 650 psig |
27.5 ≤ 45 barg |
|
2022-#38 |
|
|
650 ≤ 1,000 psig |
45 ≤ 138 barg |
IS-4 |
|
SH-4015 |
|
1,000 ≤ 1,500 psig |
138 ≤ 103 barg |
|
|
5133G |
|
1,500 ≤ 1,800 psig |
103 ≤ 124 barg |
|
|
5155G |
|
Tracer Systems |
|
||||
Stainless Steel Tubing |
|||||
0 ≤ 250 psig (≤ 650°F) |
0 ≤ 17 barg (≤ 343°C) |
IS2 |
|
2011-#38 |
|
250 ≤ 400 psig (≤ 650°F) |
17 ≤ 27.5 barg (≤ 343°C) |
|
2011-5/64 |
|
|
400 ≤ 650 psig (≤ 650°F) |
27.5 ≤ 45 barg (≤ 343°C) |
|
2022-#38 |
|
|
Unsupported Tubing |
|
||||
0 ≤ 250 psig (≤ 650°F) |
0 ≤ 17 barg (≤ 343°C) |
|
|
WMT-AB |
|
Copper Tubing |
|
||||
0 ≤ 200 psig (≤ 650°F) |
0 ≤ 14 barg (≤ 343°C) |
IS2 / IS2-BD |
|
2011N-7/64 |
|
Process Heaters |
|
||||
Positive Press - Non-Stall |
Consult Manufacturer or Local Representative |
||||
0 ≤ 650 psig up to 20,000 #/hr |
0 ≤ 45 barg up to 9072 kg/hr |
Series 300 |
|
||
650 ≤ 1,000 psig up to 20,000 #/hr |
45 ≤ 138 barg up to 9072 kg/hr |
Series 400 |
|
||
0 ≤ 465 psig up to 60,000 #/hr |
0 ≤ 32 barg up to 27215 kg/hr |
Series ICS |
|
||
0 ≤ 450 psig up to 280,000 #/hr |
0 ≤ 32 barg up to 127000 kg/hr |
Series LS & MS |
|
||
Modulating Press - Stall |
|
||||
0 ≤ 200 psig up to 4,800 #/hr |
0 ≤ 14 barg up to 2177 kg/hr |
Series DD-6 |
|
||
0 ≤ 200 psig up to 19,900 #/hr |
0 ≤ 14 barg up to 9026 kg/hr |
Series DD-12 |
|
||
Condensate From Multiple Sources - Open System |
|
||||
0 ≤ 150 psig (≤ 500°F) |
0 ≤ 10 barg (≤ 260°C) |
PT Series |
|
Applications: Turbines, Flares, Storage Tanks
Application |
1st Choice - Best Life-Cycle Performance / Cost |
||||
Valve/Strainer |
SAP/PN |
Steam Trap |
SAP/PN |
||
Connector |
|||||
Turbines |
|
||||
Inlet Control Valve Stations / Casing Drains / Exhaust Lines (Positive Pressure) |
|||||
Saturated Steam |
|||||
0 ≤ 250 psig |
0 ≤ 17 barg |
IS2 |
|
2011-#38 |
|
250 ≤ 400 psig |
17 ≤ 27.5 barg |
|
2011-5/64 |
|
|
400 ≤ 650 psig |
27.5 ≤ 45 barg |
|
2022-#38 |
|
|
650 ≤ 1,000 psig |
45 ≤ 138 barg |
|
|
421 |
|
1,000 ≤ 1,500 psig |
138 ≤ 103 barg |
|
|
5133G |
|
1,500 ≤ 1,800 psig |
103 ≤ 124 barg |
|
|
5155G |
|
Superheated Steam |
|
||||
0 ≤ 250 psig (≤ 650°F) |
0 ≤ 17 barg (≤343°C) |
IS2 / IS2-BD |
|
FF-4250 |
|
250 ≤ 450 psig (≤ 800°F) |
17 ≤ 31 barg (≤ 427°C) |
|
FF-4450 |
|
|
450 ≤ 900 psig (≤ 900°F) |
31 ≤ 62 psig (≤ 382°C) |
IS-4(BD) |
|
FF-4700 |
|
900 ≤ 1,245 psig (≤ 900°F) |
62 ≤ 86 psig (≤ 382°C) |
IS-4(BD) |
|
FF-4900 |
|
Exhaust Lines - Vacuum / Negative Differential |
Consult Manufacturer or Local Representative |
||||
≤ 150 psig |
≤ 10 barg (≤ 260°C) |
DD Series |
|
||
Flares |
|
||||
Inlet Control Valve Stations & Expansion Loops to Flare Tip |
|
||||
Saturated Steam |
|
||||
0 ≤ 650 psig |
0 ≤ 45 barg |
IS2 / IS2-BD |
|
2011(22) Series |
|
Downstream of Control Valve |
Consult Manufacturer or Local Representative |
||||
0 ≤ 200 psig (≤ 400°F) |
0 ≤ 14 barg (≤ 204°C) |
DD Series |
|
||
Multiple Steam Supplies |
Consult Manufacturer or Local Representative |
||||
0 ≤ 150 psig (≤ 500°F) |
0 ≤ 10 barg (≤ 260°C) |
PT Series |
|
||
Storage Tanks |
|
||||
Inlet Control Valve Stations |
Consult Manufacturer or Local Representative |
||||
0 ≤ 650 psig (≤ 650°F) |
0 ≤45 barg (≤ 343°C) |
IS2 / IS2-BD |
|
2011(22) Series |
|
Constant Supply Pressure |
Consult Manufacturer or Local Representative |
||||
0 ≤ 650 psig up to 20,000 #/hr |
0 ≤ 45 barg up to 9072 kg/hr |
Series 300 |
|
||
Modulating Supply Pressure |
Consult Manufacturer or Local Representative |
||||
0 ≤ 200 psig (≤ 400°F) |
0 ≤ 14 barg (≤ 204°C) |
DD Series |
|